NFPA 10 is the national standard for portable fire extinguishers — including the Class K extinguisher every commercial kitchen must keep by the cook line. Heres what it requires, how often each extinguisher must be checked, and what it takes to show yours are ready.

NFPA 10

The definition

NFPA 10 is the Standard for Portable Fire Extinguishers, published by the National Fire Protection Association. The current edition is 2026.

It governs the selection, placement, inspection, testing, and maintenance of every portable extinguisher in a building — the right type for the hazard, mounted where it can be reached, and kept in ready condition. Extinguishers are rated by the fire class they fight: A (ordinary combustibles), B (flammable liquids), C (electrical), D (metals), and K (cooking oils and fats).

A Class K extinguisher uses a wet chemical agent that forms a saponification blanket over burning cooking oil — sealing and cooling it. A standard ABC dry-chemical unit will not put out a Class K fire; the hot oil can splatter and spread.

The second layer

The Class K extinguisher in a commercial kitchen

NFPA 96 requires two layers of fire protection over the cook line, and NFPA 10 governs the second one:

  1. 01The fixed suppression system (NFPA 17A) is the primary protection — it discharges automatically on a fire.
  2. 02The Class K portable (NFPA 10) is the required backup — placed within 30 feet of the cooking equipment. It covers a flare-up after the fixed system has discharged and is offline awaiting recharge, and during cleaning or service when the fixed system is impaired.

A kitchen with a working hood and suppression system can still fail inspection if the Class K portable is missing, wrong-type, expired, or out of reach.

The schedule

How often each extinguisher must be checked

NFPA 10 sets a tiered schedule — each tier catches a different failure the one above it cant see:

CheckIntervalBy whom
Visual inspectionMonthly (every 30 days)Owner / staff
MaintenanceAnnualCertified technician
Internal examination6-yearCertified technician
Hydrostatic test5 or 12-year (by type)Certified technician

The monthly visual is the owners or property managers responsibility — not the fire companys — and missing that documentation is one of the most common inspection violations. A green gauge doesnt prove the annual maintenance was done; the tag does.

The edition

Which edition applies to you

The current edition is not necessarily the one your kitchen answers to. 2026 is the current NFPA 10 edition, but a standard only becomes enforceable when a state or local authority adopts it — on each jurisdictions own timeline. Many are still enforcing an earlier edition.

The version that governs your kitchen is the edition your state and local AHJ has adopted. Confirm the adopted edition for your jurisdiction.

The proof

What it takes to show theyre ready

An extinguisher is only protection if its the right type, in reach, and current — and you can show it. The record is what answers a fire marshal, an insurer, or an OSHA inspector; the most-cited violation in the category is a missing or expired tag, or absent monthly-inspection documentation.

  1. 01A monthly visual-inspection record for each unit, signed off on time.
  2. 02A current annual maintenance tag from a certified technician.
  3. 03Correct type and placement for each hazard — Class K within reach of the cook line.

Where EvidLY fits

EvidLY is the record layer for the fire protection systems your kitchen depends on. Every extinguishers monthly check and annual service — alongside the NFPA 17A suppression service and the NFPA 96 exhaust cleaning — is captured, dated, and held as a sealed, tamper-evident record, on the schedule each requires. When anyone asks whether the extinguishers are current, the proof is already there, in one place, not a faded tag on the wall.

Book a Demo →

NFPA 10 and the rest of your fire protection.

The Class K portable is the backup to the fixed suppression system (NFPA 17A) over your exhaust hood (NFPA 96) — together the cook-line protection your property policy may name in a Protective Safeguards Endorsement.

Common questions

NFPA 10 — FAQ

What is NFPA 10?

The Standard for Portable Fire Extinguishers — it governs the selection, placement, inspection, and maintenance of every portable extinguisher in a building. The current edition is 2026.

How often must a fire extinguisher be inspected?

A monthly visual inspection (owner or staff), plus annual maintenance by a certified technician. Stored-pressure units also need a 6-year internal exam and hydrostatic testing on a 5- or 12-year cycle by type.

Why does a commercial kitchen need a Class K extinguisher?

Class K is the only portable rated for cooking oils and fats — it forms a saponification blanket that seals and cools the oil. An ABC dry-chemical unit won’t extinguish a Class K fire. It’s placed within 30 feet of the cooking equipment.

Who is responsible for the monthly inspection?

The owner or property manager — not the fire protection company. NFPA 10 requires it every 30 days, and missing that documentation is a common inspection violation.